Creating an Efficient Liquid Cooling Solution: Design and Testing Methods of Liquid - Cooling Plates

1.1 Cold Plate

1.1.1 Description of the Cold Plate

The cold plate is a heat sink with integrated pipes or flow channels, allowing a liquid to flow through the heat sink to dissipate heat. The cold plate is installed on processors and other electronic components that require cooling, providing a path for heat to be transferred to the coolant. The design of the cold plate can be divided into single-phase or two-phase coolant types, and it can be optimized for specific coolants to maximize the heat dissipation performance. For example, a simple cold plate may be a metal block with integrated pipes, while a complex design may include milled or molded micro-flow channels to enhance the thermal performance.

 

For a cold plate assembly with integrated pipes, the cold plate typically consists of a fluid heat exchanger containing flow channels and a fixing bracket. The fluid heat exchanger is connected to the pipes through metal connection processes such as welding, brazing, or soldering. For cold plates using machined or molded flow channels, their components include a flow channel heat exchanger, a fixing bracket, and a fluid connector (Figure 1). The fluid connector is installed on the heat exchanger to guide the coolant to flow through the flow channels. The connector is fixed to the pipe with a hose clamp, while the fixing bracket provides structural support for the component stack and ensures the precise positioning of the heat exchanger on the processor.

Figure 1: Example of cold plate assembly
A cold plate heat exchanger with fluid channels consists of two parts: a cold plate base with machined or molded fluid channels and a top cover. The cold plate base and the top cover are connected through an optimally – designed manufacturing process, which needs to be adjusted according to the material characteristics of the cold plate. This ensures that the interface between the base and the top cover is completely sealed, preventing any leakage of the cold plate throughout its entire service life.

 

The fluid heat exchanger is the core cooling component of the cold plate. The fluid connector guides the coolant into the channels through pipes for circulation. The cold plate base is designed to be in direct contact with the processor. A compatible TIM2 (Thermal Interface Material 2) needs to be applied between the processor and the base to enhance the performance of the cold – plate heat dissipation solution.

 

The cold plate top cover is used to enclose the fluid channels and usually integrates a fluid connector to guide the coolant through the channels. The fluid channels are a key feature of the cold plate heat exchanger. As the coolant flows through these channels, it takes away the heat from the processor through contact with the fluid. The channels are precisely arranged between the cold plate base and the top cover. Their design typically uses machining or molding processes and is integrated into the structure of the base or the top cover to ensure the mechanical stability of the channels during the fluid flow. Figure 2 shows an example of a cold plate base with integrated machined fluid channels.
Figure 2: An example of a cold plate fluid heat exchanger

The cold plate fluid connector is installed on the fluid heat exchanger of the cold plate and serves as the interface between the cold plate and the coolant circulation. The design of the cold plate fluid connector can be optimized for specific flow rates, system dimensional tolerances, and fluid circulation configurations, while minimizing fluid stagnation. Throughout the service life of the cold plate, the design and installation of the cold plate fluid connector need to ensure a sealed and leak-free connection.


1.1.2 Types of Cold Plates


Cold plates can be divided into integrated cold plates (see Figure 3(a)) and split cold plates (see Figure 3(b)). In an integrated cold plate, the fluid heat exchanger and the retaining bracket are integrated and inseparable. Since the retaining bracket is integrated into the cold plate design, it is difficult to redeploy the integrated cold plate across different processor generations. In contrast, for a split cold plate, the fluid heat exchanger and the retaining bracket are separate components. This modular design supports redeployment across multiple processor generations by redesigning the retaining bracket suitable for the newer processor series and reusing the fluid heat exchanger, which is a cost-saving option. Schematic diagrams of the two types of cold plates are shown in Figure 3 below.

Figure 3: Examples of integrated and split cold plate types

1.1.3 Cold Plate Manufacturing and Assembly


The main manufacturing processes for the top cover plate of the heat exchanger and the cold plate base include brazing, friction stir welding, soldering, and O – ring – based sealing. Table 1 below describes some of the advantages and disadvantages of the specific manufacturing processes used for assembling the cold plate heat exchanger.

Table 1: Comparison of Cold Plate Manufacturing Processes

Manufacturing ProcessAdvantagesDisadvantages
Brazing– Supports higher working pressures
– Brazed fins can enhance rigidity
– High cost
– Need to consider the chemical compatibility of the filler metal
– Copper is annealed during brazing, reducing rigidity
Friction Stir Welding (FSW)– Supports integrated/split – type designs
– Does not cause copper annealing
– High cost
– Long process time
– Requires more material for the weld seam
Soldering– Lower cost compared to brazing/FSW
– Does not cause copper annealing
– Need to consider the compatibility of the solder
– Cannot weld fins
– Solder joints are prone to embrittlement and porosity
O – ring– Low cost
– Supports non – metallic materials
– Supports complex flow channel designs
– Low working pressure
– Poor sealing reliability
– Short service life
– Prone to leakage at high temperatures
Insufficient marginal conditions and process control during the cold plate manufacturing process may introduce defects that affect performance and reliability. The cold plate product certification plan should include representative samples from the production line to evaluate the performance and reliability of cold plates within the process control range.

 

1.2 Cold Plate Assembly


The cold plate assembly consists of a cold plate, coolant pipes, and quick connectors. Optional cold plate components include transition connectors and leak detection hardware, which can be integrated according to the customer’s product design requirements. A schematic diagram of the cold plate assembly is shown in Figure 4. The additional components required to support the cold plate are described as follows:

 

Coolant Pipes: These pipes convey coolant from the cold plate cooling circuit to the cold plate. The metal materials can be copper or aluminum, while the non – metal materials can be PTFE (Polytetrafluoroethylene), PEX (Cross – linked Polyethylene), or EPDM (Ethylene Propylene Diene Monomer). The pipe material should be selected according to the type and design of the cold plate fluid connector. Leak detection cables/ropes can be integrated by winding them around the fluid pipes and cold plate connectors.

 

Quick Connectors: They support the quick disconnection of the cold plate from the cooling circuit and IT equipment, facilitating maintenance operations.

 

Transition Connectors (Optional): These are used to connect the coolant pipes to the quick connectors in the cold plate assembly.

 

Leak Detection (Highly Recommended): It alerts the data center operators when a leak is detected.
Figure 4: Example of Cold Plate Assembly

1.3 Cold Plate Technology Cooling System
The cold plate technology cooling system consists of IT equipment (ITE), cold plates, coolant piping, quick disconnects (QDs), blade manifolds, secondary cooling loops, coolant distribution units (CDUs), facility water systems (FWS), and cooling towers or chillers. This system supplies coolant to the cold plates at a constant temperature and pressure. Figure 5 illustrates a schematic diagram of a cold plate liquid cooling system. All wetted materials in the cold plate technology cooling system must be compatible with the coolant.

Figure 5: Schematic Diagram of Cold Plate Liquid Cooling Loop (Technology Cooling System—TCS)

Latest Blog

From Concept to Mass Production – Your Professional Heat Dissipation Solution Partner

Scroll to Top

contact Ecotherm

We are available to assist you via email. Please don’t hesitate to get in touch, and we will respond to your inquiry as soon as possible.


Email:  support@ecothermgroup.com

Follow us on YouTube | TikTok | LinkedIn
Stay connected with us for updates, news, and more!


Please fill out the form below, and we will get back to you as soon as possible.

Contact Ecotherm

Please upload your design or requirements, and our experts will provide a precise cooling solution tailored to your needs.